EasyManua.ls Logo

Siemens Reyrolle 7SR5 - Page 62

Siemens Reyrolle 7SR5
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter: VT1/2/3 Ratio Prim
•
Default setting: 132000 V
The setting value is used (in conjunction with VT1/2/3 Ratio Sec setting) by the device instrumenta-
tion e.g. to display primary voltage values.
Parameter: VT1/2/3 Ratio Sec
•
Default setting: 110 V
The setting value is used (in conjunction with VT1/2/3 Ratio Prim setting) by the device instrumen-
tation e.g. to display primary voltage values.
Parameter: VT1/2/3 Nominal
•
Default setting: 63.5 V
This is set to the rated voltage applied to the VT input. The setting will be dependent on the VT Config
setting e.g. phase-phase or phase-neutral Volts may be connected to the VT inputs.
Device Functionality
3.3 CT and VT Inputs
62 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Other manuals for Siemens Reyrolle 7SR5

Related product manuals