EasyManua.ls Logo

Siemens Reyrolle 7SR5 - Page 69

Siemens Reyrolle 7SR5
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter: Enabled in Local
•
Default Setting: <All>
Operation of the selected binary input is enabled when Device Config > Operating Mode is
selected to Local, (see 3.2 Device Configuration ).
Parameter: Enabled in Remote
•
Default Setting: <All>
Operation of the selected binary input is enabled when Device Config > Operating Mode is
selected to Remote, (see 3.2 Device Configuration ).
Parameter: Enabled in Out of Service
•
Default Setting: <All>
Operation of the selected binary input is enabled when Device Config > Operating Mode is
selected to Out of Service, (see 3.2 Device Configuration ).
Parameter: Inhibit <Function>
•
Default Setting: <None>
When operated the binary input initiates the reset sequence of the relevant function element(s).
Parameter: Ext Trig 60VTS
•
Default Setting: <None>
Used to initiate the VT supervision function (60VTS) time delay element from a MCB connected in the VT
secondary circuit, (see 6 Supervision Functions , section 60VTS VT Supervision).
Parameter: Ext Reset 60VTS
•
Default Setting:
Used to reset the VT supervision function (60VTS) when a VT failure condition no longer exists, (see
6 Supervision Functions , section 60VTS VT Supervision).
Parameter: 50BF-n CB Faulty
•
Default Setting: <None>
This input is connected to the CB monitoring circuits. If this input is operated when a trip initiation is
received an output will be given immediately (the timers are by passed), (see 6 Supervision Functions ,
section 50BF Circuit-Breaker Failure Protection – 3 Pole).
Parameter: 50BF-n Mech Trip
•
Default Setting: <None>
Used to trigger the circuit‑breaker fail function. A binary input configured as CB Closed must also be
energized to confirm CB failure, (see 6 Supervision Functions , section 50BF Circuit-Breaker Failure
Protection – 3 Pole).
Device Functionality
3.4 Binary Inputs
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 69
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Other manuals for Siemens Reyrolle 7SR5

Related product manuals