EasyManua.ls Logo

Siemens Reyrolle 7SR5 - Page 93

Siemens Reyrolle 7SR5
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PTRC1.Tr
Information
Trip operated (as configured to trip contact) 0 1
PTRC1.Tr.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value FALSE: 0
TRUE: 1
PTRC1.OpCntRs
Information
Resettable operations counter Measured Value
PTRC1.OpCntRs.stVal Value
Virtual Inputs/Outputs
VGGIO1.Mod
Information
Reset Device x
VGGIO1.Mod.stVal 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
VGGIO1.Health
Information
Device Healthy 0 1
VGGIO1.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
Device Functionality
3.5 Binary Outputs
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 93
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Other manuals for Siemens Reyrolle 7SR5

Related product manuals