4/8
Siemens Building Technologies CC1N7865en
HVAC Products 20.11.2002
Technical data
Mains voltage AC 100...240 V ±10 %
Mains frequency 50...60 Hz
Safety class II to DIN 0631
Mounting position optional
Terminals for 2 x 1.5 mm² or 1 x 2.5 mm²
Power consumption approx. 8 VA
Safety extra low-voltage DC 24 V
Contact rating of the control outputs
(relays «K1...K3»)
- Up to 2 x 10
5
switching cycles
- Up to 10
7
switching cycles
2 A / AC 24...240 V
0.1 A / AC 24...240 V
Weight complete with housing approx. 760 g
Recommended actuator running time 15...60 s
Degree of protection of housing
- Front
- Base
IP 65, EN 60529
IP 20, EN 60529
Transport
Temperature range -40...+70 °C
Humidity < 75 % r.h.
Operation
Temperature range -20...+50 °C
Humidity < 75 % r.h.
Condensation, formation of ice and ingress of water are not permitted!
General controller data
Environmental
conditions