EasyManuals Logo

Siemens SBA 2000 User Manual

Siemens SBA 2000
103 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #99 background imageLoading...
Page #99 background image
Ordering Information
97
External Accessories
Key Interlocks
Accessory Catalog Number
Installed on Breaker
Provision only
Circuit Breaker
Drawout
KISB, SISB
KIPOF
SKIPOD, 20KIPOD
Remote Indication Panel
Accessory Catalog Number
Remote Indication Relay Panel SBRIP
Display Module
Accessory Catalog Number
Display Module SBDM
Ground Fault Display Module
Accessory Catalog Number
Ground Fault Display Module SBGFM
Auxiliary Power Source For Electronic Trip
Unit
Accessory Catalog Number
Auxiliary Power Source SBAPM
Universal Trip Unit Test Kit
Accessory Catalog Number
Test Kit TS31
UL Listings and File Numbers
UL Listing File Number
Trip Unit
Breaker
Draw Assembly
Accessories
CSA Guides
E9896
E9896
E135453
E57501
LR57039
Time Current Curves
Description Catalog Number
Time Current Curves TD7210
Electric Operator Troubleshooting Guide
Symptom Solutions
Motor does not run. 1. Check for springs already charged by checking spring charge indicator.
2. Check for rated voltage at LT1 and LT5.
3. Check motor fuse - requires 1.8A Slo-Blo fuse.
4. Check all wiring connections.
5. If the lamp connected to LT4 is blinking slowly (one second on, two seconds off) remove power from LT1 and LT5 then
re-apply power
Motor runs for 20 seconds, does not charge
springs, lamp on LT4 blinks slowly (one
second on, two seconds off).
1. Remove power from LT1 and LT5, manually charge breaker. Reapply power to LT1 and LT5 motor should run for less than
10 seconds and shut off. Lamp on LT4 should remain on.
Breaker will not close electrically. 1. Check to see if springs are charged by checking charged indicator flag.
2. Check for power on LT1 and LT5.
3. Check for power on LT2. If power is on LT2, remove and reapply.
4. Check to see if breaker is locked in open position by either padlocking device, kirk key, or drawout interlock.
5. Check all wiring connections.
Lamp on LT4 blinks slowly (one second on,
two seconds off).
1. Remove power from LT1 and LT5, manually charge breaker springs. Reapply power to LT1 and LT5. Lamp on LT4 should
remain on.
Mechanical Interlock
Accessory Catalog Number
800A, 1200A Envelope
Fixed Circuit Breaker
Drawout Circuit Breaker
SBMIF08
SBMID08
2000A Envelope
Fixed Circuit Breaker
Drawout Circuit Breaker
SBMIF20
SBMID20
Cell Switches
Accessory Catalog Number
1A & 1B
2A & 2B
3A & 3B
4A & 4B
CEL1
CEL2
CEL3
CEL4
Capacitor Trip
Accessory Catalog Number
Capacitor Trip Consult Siemens
Breaker Closing Blocking Device
Accessory Catalog Number
Breaker Closing Blocking Device SBBD
Padlock Devices
Accessory Catalog Number
Installed on Breaker
Installed on Drawout
SBPLB
SBPLD
Courtesy of NationalSwitchgear.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SBA 2000 and is the answer not in the manual?

Siemens SBA 2000 Specifications

General IconGeneral
BrandSiemens
ModelSBA 2000
CategoryCircuit breakers
LanguageEnglish

Related product manuals