Instrument transformers
Current transformers (CTs)
Figure 5: Type SDV6 distribution circuit 
breaker with interphase barriers and 
bushing current transformers installed in 
primary compartment on page 17 
illustrates bushing (toroidal) CTs installed 
in the primary compartment of a type 
SDV6 distribution circuit breaker. The roof 
bushings pass through the CTs. Up to two 
CTs may be mounted around each roof 
bushing. The bushing CT connections are 
wired to separate terminal blocks located 
in the low-voltage operator compartment. 
Phase barriers
Phase barriers are provided on all 27.6 kV 
and 38.0 kV class type SDV6 distribution 
circuit breakers as shown in Type SDV6 
distribution circuit breaker with interphase 
barriers and bushing current transformers 
installed in primary compartment on page 
17. These plates of insulating material are 
attached to the circuit breaker housing and 
provide suitable electrical insulation 
between the vacuum interrupter primary 
circuits. 
Hazardous voltages.
Will cause death, serious injury or property damage.
Do not operate current transformers with the secondary open-
circuited. Current transformers must be either connected to a 
load or short circuited. Current transformer secondary circuits 
also must be grounded.
16