Installation
Introduction
This section provides a description of the 
inspections, checks and tests to perform 
on the type SDV6 distribution circuit 
breaker prior to operation.
Inspections, checks and tests without 
control power
Type SDV6 vacuum circuit breakers are 
normally shipped with the primary 
contacts open and the springs discharged. 
However, prior to starting the inspection 
process, it is critical to first verify that the 
control power is de-energized, the spring-
loaded mechanisms are in the discharged 
condition and the circuit breaker main 
contacts are open.
De-energizing control power in a power 
circuit breaker
To de-energize the control power, open the 
disconnect device in the low-voltage 
compartment. Figure 6: Low-voltage 
compartment presents the location of this 
disconnect in a standard type SDV6 
distribution circuit breaker.
The control power disconnect device is 
located on the control panel in the low-
voltage compartment.
Figure 5: Type SDV6 distribution circuit 
breaker with interphase barriers and 
bushing current transformers installed in 
primary compartment on page 17 shows a 
knife switch with fuses. Opening the knife 
switch de-energizes control power to the 
circuit breaker. In some circuit breakers, 
pullout type fuse holders or molded-case 
circuit breakers are used in lieu of knife 
switches. Removal of the fuse holder or 
opening the molded-case circuit breaker 
accomplishes the same result: control 
power is disconnected.
Spring discharge check (refer to Figure 
6: Low-voltage compartment on page 
19)
1.    De-energize control power.
2.    Press red open button on the operating 
mechanism.
3.    Press black close button on the 
operating mechanism.
4.    Again press red open button on the 
operating mechanism.
5.    Verify spring condition indicator shows 
DISCHARGED.
6.    Verify main contact status indicator 
shows OPEN.
Physical inspections
1.    Verify the rating of the circuit breaker 
is compatible with the system.
2.    Perform a visual shipping damage 
check. Clean the circuit breaker of all 
shipping dust, dirt and foreign 
material.
Hazardous voltages and high speed moving parts.
Will cause death, serious injury or property damage.
Read instruction manuals, observe safety instructions and use 
qualified personnel.
18