Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Mechanical installation 01.2002
3.3.3 Mounting SED2 drives with IP20/NEMA 0 rating
H
H
H
W
W
Frame size A
Frame size B
Frame sizes D, E and F
5192M01en
Hole spacing
Frame size
H in mm W in mm
Mounting materials
Tightening
torque
A
160
* 187
-
*56
2 x M4 bolts
2 x M4 nuts
2
x M4 spring lock washers
2 x M4 washers
or mounting on DIN rail
2.5 Nm
B
174
* 200
138
* 120
4
x M4 bolts
4 x M4 nuts
4
x M4 spring lock washers
4
x M4 washers
2.5 Nm
C
204
* 232
174
* 156
4
x M5 bolts
4 x M5 nuts
4
x M5 spring lock washers
4
x M5 washers
3.0 Nm
D 486 235
4
x M8 bolts
4 x M8 nuts
4
x M8 spring lock washers
4
x M8 washers
13 Nm
E
616.4 235
4
x M8 bolts
4 x M8 nuts
4
x M8 spring lock washers
4
x M8 washers
13 Nm
F
810
1110withfilter
300
4
x M8 bolts
4 x M8 nuts
4
x M8 spring lock washers
4
x M8 washers
25 Nm
* with footprint filter
A minimum clearance of 100 mm is required above and below each variable speed
drive.
Drilling plan for SED2
IP20
Note
.
..
.