Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
31=MOP setpoint + Fixed frequency
32=Analog setpoint + Fixed frequency
33=Fixed frequency + Fixed frequency
34=USS on BOP link + Fixed frequency
35=USS on COM link + Fixed frequency
36=CB on COM link + Fixed frequency
37=Analog setpoint 2 + Fixed frequency
71=MOP setpoint + Analog setpoint 2
72=Analog setpoint + Analog setpoint 2
73=Fixed frequency + Analog setpoint 2
74=USS on BOP link + Analog setpoint 2
75=USS on COM link + Analog setpoint 2
76=CB on COM link + Analog setpoint 2
77=Analog setpoint 2 + Analog setpoint 2
Index:
P1000[0] : 1st command data set (CDS)
P1000[1] : 2nd command data set (CDS)
Note:
Single digits denote main setpoints that have no additional setpoint.
P1001 Fixed frequency 1
Defines fixed frequency setpoint 1.
Unit: Hz Min: -650.0 Def: 0.00 Max: 650.00
Level 3
There are 3 types of fixed frequencies:
1. Direct selection (P0701 - P0706=15)
In this mode of operation 1 digital input selects 1 fixed frequency. If several inputs are active together, the selected
frequencies are summed, e.g., FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
2. Direct selection + ON command (P0701 - P0706=16)
The fixed frequency selection combines the fixed frequencies with an ON command. In this mode of operation 1
digital input selects 1 fixed frequency. If several inputs are active together, the selected frequencies are summed,
e.g., FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
3. Binary coded selection + ON command (P0701 - P0706=17)
Select up to 16 fixed frequencies using this method. Select the fixed frequencies according to the following table:
DIN4 DIN3 DIN2 DIN1
OFF Inactive Inactive Inactive Inactive
P1001 FF1 Inactive Inactive Inactive
Active
P1002 FF2 Inactive Inactive
Active
Inactive
P1003 FF3 Inactive Inactive
Active Active
P1004 FF4 Inactive
Active
Inactive Inactive
P1005 FF5 Inactive
Active
Inactive
Active
P1006 FF6 Inactive
Active Active
Inactive
P1007 FF7 Inactive
Active Active Active
P1008 FF8
Active
Inactive Inactive Inactive
P1009 FF9
Active
Inactive Inactive
Active
P1010 FF10
Active
Inactive
Active
Inactive
P1011 FF11
Active
Inactive
Active Active
P1012 FF12
Active Active
Inactive Inactive
P1013 FF13
Active Active
Inactive
Active
P1014 FF14
Active Active Active Active
Data:
P1015 FF15
Active Active Active Active
Dependency:
Select fixed frequency operation (using P1000).
Variable speed drive requires ON command to start in the case of direct selection (P0701 to P0706=15).
Note:
Fixed frequencies can be selected using the digital inputs, and can also be combined with an ON command.
P1002-P1015 Fixed frequency 2 through 15
Defines fixed frequency setpoint 2.
Unit: Hz Min: -650.00 Def: See Note below Max: 650.00
Level 3
Details:
See P1001 (fixed frequency 1).
Default fixed frequency setpoint values are as follows:
Fixed Frequency Default Fixed Frequency Default Fixed Frequency Default
1 0.00 6 25.00 11 50.00
2 5.00 7 30.00 12 55.00
3 10.00 8 35.00 13 60.00
4 15.00 9 40.00 14 65.00
Note:
5 20.00 10 45.00 15 65.00
P1016 to
P1019
Fixed frequency mode - Bit 0 through 3
Fixed frequencies can be selected in three different modes. Parameter P1016 defines the
mode of selection Bit 0.
Unit: - Min: 1 Def: 1 Max: 3
Level 3
Details:
Parameter P1016 defines the mode of Bit 0, Parameter P1017 defines the mode of Bit 1, Parameter P1018 defines the
mode of Bit 2, and Parameter P1019 defines the mode of Bit 3.
Settings:
1=Direct selection 2=Direct selection + ON command 3=Binary coded selection + ON command
Note:
See table in P1001 (fixed frequency 1) for a description of how to use fixed frequencies.
P1020[2] to
P1023[2]
BI: Fixed frequency selection Bit 0
Defines origin of fixed frequency selection.
Unit: - Min: 0:0 Def: 0:0 (P1023 = 722:3) Max: 4000:0
Level 3
Settings:
P1020= 722.0 ==> Digital input 1
P1021= 722.1 ==> Digital input 2
P1022= 722.2 ==> Digital input 3
P1023= 722.3 ==> Digital input 4
P1026= 722.4 ==> Digital input 5
P1028= 722.5 ==> Digital input 6
Index:
P1020[0] : 1st command data set (CDS) for Bit 0
P1021[0] : 1st command data set (CDS) for Bit 1
P1022[0] : 1st command data set (CDS) for Bit 2
P1023[0] : 1st command data set (CDS) for Bit 3
P1020[1] : 2nd command data set (CDS) for Bit 0
P1021[1] : 2nd command data set (CDS) for Bit 1
P1022[1] : 2nd command data set (CDS) for Bit 2
P1023[1] : 2nd command data set (CDS) for Bit 3