Accessories
3.2 Electromechanical accessories
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
100 Manual, 10/2018, L1V30499596002-01
Undervoltage release (UVR)
The undervoltage release trips the circuit breaker if the rated control supply voltage U
s
fails
or drops to between 70% and 35% of its normal value (in compliance with the relevant
standard). The undervoltage release can be used for:
Safe remote tripping
Interlocking during closure
Checking the voltage in the primary and secondary circuits
The undervoltage release is powered via the auxiliary conductor terminal system.
Note
The circuit breaker can be reclosed at a coil supply voltage of 85% to 110%
U
n
.
Suitable for continuous operation: 100% ON time
Technical specifications
AC
DC
Rated control supply voltage U
s
24 V
30 V
48 V
60 V
110 to 120 V
120 to 127 V
220 to 240 V
240 to 250 V
380 to 400 V
415 to 440 V
Operating limits UVR: ON: 85 to 110% U
s
UVR: OFF: ...< 70% U
s
Switch-on power 300 VA 300 W
Continuous power
3.5 VA
3.5 W
Break time UVR
30 ms