Accessories   
3.5 External accessories 
  3VA27 molded case circuit breakers & 3WL10 air circuit breakers 
120  Manual, 10/2018, L1V30499596002-01 
 
External CT for grounding conductors of the main power supply (grounded transformer 
star point) G_ret using the ground fault return 
Currents in the grounding conductor of the transformer star point can be directly measured 
with high accuracy using this toroidal-core transformer and can be evaluated with the 
ETU660 (LSIG). The transformer is connected to the auxiliary conductor terminal system of 
the circuit breaker. The external current transformer for the grounding conductor of the 
power supply is available with rated currents 100 A and 250 A.  
Direct measurement of ground currents is an alternative to the vector sum calculation. 
 
T6 
External CT for grounding conductors of the main power supply (grounded transformer star 
 
Summation current transformer Rc CT 
Residual currents of 3 A to 30 A can be measured with a summation current transformer and 
evaluated by electronic trip units of the 6-series, which is equipped with a rating plug for 
residual current protection and the metering function MF Advanced. The transformer is 
connected to the auxiliary conductor terminal system of the circuit breaker.  
 
Summation current transformer