Application planning
4.1 Types of installation and installation locations
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Manual, 10/2018, L1V30499596002-01
143
Current reduction depending on the ambient temperature on the 3VA27
Fixed-mounted
for
● Rear vertical main circuit connection
● Broadened bus connectors
● Front circular conductor terminal for CuAl cables (4x240 mm²)
Rated opera-
tional current
I
n
[A]
Min. cop-
per cross
section
[mm
2
]
800 500
1000 600
100% 100% 100% 100% 100% 95% 89%
1250 800
100% 100% 100% 100% 95% 90% 85%
1600 1000
for
● Straight bus connectors extended
● Rear horizontal main circuit connection
Rated opera-
tional current
I
n
[A]
Min. cop-
per cross
section
[mm
2
]
800 500
1000 600
1250 800
1600 1000
for
● Nut keeper kit