Connection and commissioning
5.2 Mounting and connecting the device
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
172 Manual, 10/2018, L1V30499596002-01
5.2.3
Fixed breaker: Installing the circuit breaker
1. Mount the circuit breaker in the switchboard panel:
Floor mounting
: (For the drilling template, see Chapter Switchboard panel, hole and
drilling templates, fixed breaker (Page 228)):
Mount the supports for floor fixation on the circuit breaker following the relevant
Operating Instructions (see Chapter Reference documents (Page 10)).
Fasten the circuit breaker to the compartment floor of the switchboard panel with four
screws M5 x 25 with a tightening torque of 4 Nm.
Note
The mounting supports are not p
art of the basic circuit breaker, but can be configured
onto the device via the Z option and ordered separately.