11
s l SEM3™ Metered Bus Plug for SENTRON Busway Systems
Single
Phase
Monitor
Modbus
Addresses
3 Position
Rack Rotary
Switch
Setting
3 Position
Rack
Modbus
Addresses
6 Position
Rack Rotary
Switch
Setting
6 Position
Rack
Modbus
Addresses
1
0
1
0*
1
2 2 2
3 3 3
4 4
5
1
5 5
6 6 6
7 7
8
9
2
9
1*
9
10 10 10
11 11 11
12 12
13
3
13 13
14 14 14
15 15
16
17
4
17
2
17
18 18 18
19 19 19
20 20
21
5
21 21
22 22 22
23 23
24
25
6
25
3
25
26 26 26
27 27 27
28 28
29
7
29 29
30 30 30
31 31
32
Single
Phase
Monitor
Modbus
Addresses
3 Position
Rack Rotary
Switch
Setting
3 Position
Rack
Modbus
Addresses
6 Position
Rack Rotary
Switch
Setting
6 Position
Rack
Modbus
Addresses
33
8
33
4
33
34 34 34
35 35 35
36 36
37
9
37 37
38 38 38
39 39
40
41
A
41
5
41
42 42 42
43 43 43
44 44
45
B
45 45
46 46 46
47 47
48
49
C
49
6
49
50 50 50
51 51 51
52 52
53
D
53 53
54 54 54
55 55
56
57
E
57
7
57
58 58 58
59 59 59
60 60
61
F
61 61
62 62 62
63 63
*Rotary switch adressing setting of 0 is identical to that of 8, similarly 1 is identical to 9. This means racks with switch settings of 0 and 8 or 1 and 9 cannot be
connected to the same controller for the six meter module racks.
Table 1: Modbus Addressing for Meter Modules
Table 1 illustrates the Modbus Addressing Schemes as a function of rotary switch settings for both the three and six meter module
rack bus plugs.
Once the rotary switch has been set, replace the bus plug covers and properly label the plug’s rack setting and controller on the
cover label. It is now safe to turn the breakers to the ON position.