Chapter 1
Turbine Package System Overview
1-18
Temperature Monitoring
A temperature transmitter (TT6) monitors the gas fuel supply temperature upstream of the gas
fuel control valve(s). The transmitter relays temperature information to the ECU and
programmable controller and provides low and high temperature shutdown signals.
Burner Instrumentation
Six temperature sensors (TC255–TC260) mounted in each of the burner assemblies continuously
monitor burner operation and provide operational data to the turbine control system.
Fuel System Requirements
Refer to the SIEMENS Fluids Specification 65/0027, which is located in this Manual Volume,
for more specific information on fuel requirements.