EasyManua.ls Logo

Siemens SICAM P38 - Page 59

Siemens SICAM P38
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication
6.2.4 Information mapping table
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018
59
Parameter List of Maximum Demand
T5 reactive power
high16 bits
2124 H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 varh
T5 reactive power
low16 bits
2125 H
T6 reactive power
high16 bits
2126 H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 varh
T6 reactive power
low16 bits
2127 H
Parameter Address Data Type Length R/W Data Range Unit
Parameter Address Data Type Length R/W Data Range Unit
Total maximum demand of current month
Import active demand 3000 H unsigned int 2 bytes R 0 ... 65535 W
Occurrence time 3001 H unsigned int 2 bytes R 0 ... 65535 Year
Occurrence time 3002 H unsigned int 2 bytes R 1 ... 12 Month
Occurrence time 3003 H unsigned int 2 bytes R 1 ... 31 Day
Occurrence time 3004 H unsigned int 2 bytes R 0 ... 23 Hour
Occurrence time 3005 H unsigned int 2 bytes R 0 ... 59 Minute
Occurrence time 3006 H unsigned int 2 bytes R 0 ... 59 Second
Import active T1
demand
3007 H ...
300D H
unsigned int
Same as import
active demand
Import active Tn
demand
... unsigned int
Same as import
active demand
Import active T6
demand
302A H ...
3030 H
unsigned int
Same as import
active demand
Export active demand
3031 H ...
3037 H
unsigned int
Same as import
active demand
Export active T1
demand
3038 H ...
303E H
unsigned int
Same as import
active demand
Export active Tn
demand
... unsigned int
Same as import
active demand
Export active T6
demand
305B H ...
3061 H
unsigned int
Same as import
active demand
Combined reactive 1
demand
3062 H ...
3068 H
unsigned int
Same as import
active demand
var
Combined reactive
1T1 demand
3069 H ...
306F H
unsigned int
Same as import
active demand
Combined reactive
1Tn demand
... unsigned int
Same as import
active demand
Combined reactive
1T6 demand
308C H ...
3092 H
unsigned int
Same as import
active demand
Combined reactive 2
demand
3093 H ...
3099 H
unsigned int
Same as import
active demand
Combined reactive
2T1 demand
309A H ...
30A0 H
unsigned int
Same as import
active demand
Combined reactive
2Tn demand
... unsigned int
Same as import
active demand
Combined reactive
2T6 demand
30BD H ...
30C3 H
unsigned int
Same
as import
acti
ve demand
Import apparent
demand
30C4 H ...
30CA H
unsigned int
Same as import
active demand
VA

Related product manuals