Operation and Display
4.3 Key Definition
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018
32
Key Setting Parameters
1. Key functions at parameter setting mode
Example 14:
This screen shows B display area (software version).
At cyclic display mode, press "▲" or "▼" to enter key display
mode, press " " to switch to area B. Press "▲" or "▼" to
switch to software version number display. "Soft" means soft-
ware version, "13" means product specification, "1210119"
means software version date and "00" means serial number of
software production. Press " " to enter second level dis-
play. You can press "▲" or "▼" to view active pulse constant,
reactive pulse constant, Modbus communication address.
Press " " to return to previous display.
Example 15:
This screen shows A display area (current unbalance rate)
and B display area (error code).
At cyclic display mode, press "▲" or "▼" to enter key display
mode. When A is selected, press "▲" or "▼" switch to current
unbalance rate option.
In the figure of A, current unbalance rate = 1.46%. Press
" " to switch to area B. Press "▲" or "▼" to switch to error
code display. "E" means error prompt, the 7 bits from right to
left mean respectively Phase A loss, Phase B loss, Phase C
loss, voltage phase reverse, Phase A current reverse, Phase
B current reverse, Phase C current reverse. For example,
"E0000001" means phase C current reverse fault occurs.
Key symbol ▲▼
Function
a) "▲" to switch digit or flip over;
b) "▼" to move cursor or flip over.
a) Press " " and " " at the same time to enter
setting screen.
b) Press " " to enter next menu or "confirm" parameter
setting.
c) Press " " to return to previous menu or "cancel" pa-
rameter setting
1
.
1.Press " " once after adjusting parameters with "▲" and "▼" to display "Sure", and press " " once
again to alter parameters. Pressing " " immediately after "Sure" appears will cancel current alteration.