6.2.4 Information mapping table
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018
53
Phase A voltage 2
nd
har-
monic ratio
1303 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase B voltage 2
nd
har-
monic ratio
1304 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase C voltage 2
nd
harmonic ratio
1305 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase A voltage No. n
harmonic ratio
... unsigned int 2 bytes R 0 ... 10000 0.01%
Phase B voltage No. n
harmonic ratio
... unsigned int 2 bytes R 0 ... 10000 0.01%
Phase C voltage No. n
harmonic ratio
... unsigned int 2 bytes R 0 ... 10000 0.01%
Phase A voltage 50
th
harmonic ratio
1393 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase B voltage 50
th
harmonic ratio
1394 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase C voltage 50
th
harmonic ratio
1395 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase A current 2
nd
har-
monic ratio
1403 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase B current 2
nd
har-
monic ratio
1404 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase C current 2
nd
har-
monic ratio
1405 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase A current No. n
harmonic ratio
... unsigned int 2 bytes R 0 ... 10000 0.01%
Phase B current No. n
harmonic ratio
... unsigned int 2 bytes R 0 ... 10000 0.01%
Phase C current No. n
harmonic ratio
... unsigned int 2 bytes R 0 ... 10000 0.01%
Phase A current 50
th
harmonic ratio
1493 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase B current 50
th
harmonic ratio
1494 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase C current 50
th
harmonic ratio
1495 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase A voltage wave-
form distortion
1500 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase B voltage wave-
form distortion
1501 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase C voltage wave-
form distortion
1502 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase A current wave-
form distortion
1503 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase B current wave-
form distortion
1504 H unsigned int 2 bytes R 0 ... 10000 0.01%
Phase C current wave-
form distortion
1505 H unsigned int 2 bytes R 0 ... 10000 0.01%
Parameter Address Data Type Length R/W Data Range Unit