Communication
6.2.4 Information mapping table
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018
56
Power Parameters
Parameter Address Data Type Length R/W Data Range Unit
Phase A active power
high 16 bits
2000 H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 Wh
Phase A active power
low 16 bits
2001 H
Phase B active power
high 16 bits
2002 H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 Wh
Phase B active power
low 16 bits
2003 H
Phase C active power
high 16 bits
2004 H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 Wh
Phase C active power
low 16 bits
2005 H
Total active power high
16 bits
2006 H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 Wh
Total active power low
16 bits
2007 H
Phase A reactive
power high 16 bits
2008 H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 varh
Phase A reactive
power low 16 bits
2009 H
Phase B reactive
power high 16 bits
200A H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 varh
Import Phase B reactive
power low 16 bits
200B H
Phase C reactive
power high 16 bits
200C H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 varh
Phase C reactive
power low 16 bits
200D H
Total reactive power
high 16 bits
200E H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 varh
Total reactive power
low 16 bits
200F H
T1 active power high16
bits
2010 H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 Wh
T1 active power low16
bits
2011 H
T2 active power high16
bits
2012 H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 Wh
T2 active power low16
bits
2013 H
T3 active power high16
bits
2014 H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 Wh
T3 active power low16
bits
2015 H
T4
active power high16
bits
2016 H
unsigned
long
4 bytes R 0 ... 4294967295 0.1 Wh
T4 active power low16
bits
2017 H

Related product manuals