EasyManua.ls Logo

Siemens SICAM P39 - Page 62

Siemens SICAM P39
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication
6.2.4 Information mapping table
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018
62
Minimum
Phase A voltage
4100 H ...
4106 H
Same as Phase
A voltage
0.01 V
Phase B voltage
4107 H
...410D H
Same as Phase
A voltage
Phase C voltage
410E H ...
4114 H
Same as Phase
A voltage
0.01 V
Uab line voltage
4115 H ...
411B H
Same as Phase
A voltage
Ubc line voltage
411C H ...
4122 H
Same as Phase
A voltage
Uca line voltage
4123 H ...
4129 H
Same as Phase
A voltage
Phase A current
412A H ...
4130 H
Same as Phase
A voltage
0.001 A
Phase B current
4131 H ...
4137 H
Same as Phase
A voltage
Phase C current
4138 H ...
413E H
Same as Phase
A voltage
Neutral current
413F H ...
4145 H
Same as Phase
A voltage
Phase A active
power
4146 H ...
414C H
Same as Phase
A voltage
1 W
Phase B active
power
414D H ...
4153 H
Same as Phase
A voltage
Phase C active
power
4154 H ...
415A H
Same as Phase
A voltage
Total active power
415B H ...
4161 H
Same as Phase
A voltage
Phase A reactive
power
4162 H ...
4168 H
Same as Phase
A voltage
1 var
Phase B reactive
power
4169 H ...
416F H
Same as Phase
A voltage
Phase C reactive
power
4170 H ...
4176 H
Same as Phase
A voltage
Total reactive
power
4177 H ...
417D H
Same as Phase
A volt
age
Phase A appa
rent
power
417E H ...
4184 H
Same as Phase
A voltage
1 VA
Phase B apparent
power
4185 H ...
418B H
Same as Phase
A voltage
Phase C apparent
power
418C H ...
4192 H
Same as Phase
A voltage
Total apparent
power
4193 H ...
4199 H
Same as Phase
A voltage
Parameter Address Data Type Length R/W Data Range Unit