Siemens Energy & Automation, Inc.
11
* See Appendix B for Motor Power Ratings at 60vC.
Each controller has two ratings: “In Line” and “Inside Delta.”
Inside Delta ratings are higher than In Line ratings.
Be sure to select equipment with the proper ratings for
the type of connections used.
For 24 Vdc replace the “?” in the catalog no. with “2”.
For 120 Vac replace the “?” in the catalog no. with “3”.
For 230 Vac replace the “?” in the catalog no. with “4”.
Table 2 - Motor Power Ratings (Kilowatts) TU = 40vC*
Catalog In Line Inside Delta
Number le in Amps Kw Voltage Amps Kw Voltage
3RW3454-0DC34 57 15/30 230/400 110 30/55 230/400
3RW3455-0DC34 70 18.5/37 230/400 135 37/75 230/400
3RW3456-0DC34 81 22/45 230/400 162 45/90 230/400
3RW3457-0DC34 110 30/55 230/400 205 55/110 230/400
3RW3458-0DC34 135 37/75 230/400 235 75/132 230/400
3RW3465-0DC34 162 45/90 230/400 285 90/160 230/400
3RW3466-0DC34 195 55/110 230/400 352 110/200 230/400
3RW3467-0DC34 235 75/132 230/400 450 132/250 230/400
3RW3472-0DC34 352 110/200 230/400 608 200/355 230/400
3RW3483-0DC34 500 160/250 230/400 865 250/500 230/400
3RW3484-0DC34 700 220/400 230/400 1216 400/710 230/400
3RW3486-0DC34 1050 375/630 230/400 1720 560/1000 230/400
3RW3452-0DC35 36 18.5/22 400/500 61 30/37 400/500
3RW3454-0DC35 57 30/37 400/500 110 55/75 400/500
3RW3455-0DC35 70 37/45 400/500 135 75/90 400/500
3RW3456-0DC35 81 45/55 400/500 162 90/110 400/500
3RW3457-0DC35 110 55/75 400/500 205 110/132 400/500
3RW3458-0DC35 135 75/90 400/500 235 132/160 400/500
3RW3465-0DC35 162 90/110 400/500 285 160/200 400/500
3RW3466-0DC35 195 110/132 400/500 352 200/220 400/500
3RW3467-0DC35 235 132/160 400/500 450 250/355 400/500
3RW3472-0DC35 352 200/220 400/500 608 355/400 400/500
3RW3483-0DC35 500 250/355 400/500 865 500/560 400/500
3RW3484-0DC35 700 400/500 400/500 1216 710/840 400/500
3RW3486-0DC35 1050 630/700 400/500 1720 1000/1200 400/500