EasyManua.ls Logo

Siemens SIMATIC 500 Series - 7 Technical Data

Siemens SIMATIC 500 Series
47 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
7 Technical Data
Version 2.1 10/01
OLM Module P11 G11 G11-1300
P12 G12 G12-1300
G12-EEC
Voltage/power supply
Operating voltage 18 V to 32 VDC, typ. 24 VDC, (redundant inputs uncoupled),
safety extra-low voltage, indirect-coupled
Current consumption max. 200 mA
Output voltage/current for terminal 5 VDC +5%,10%/ 90 mA; short circuit-proof
resistors (Pin 6 Sub-D socket)
Signaling contact
Maximum switch voltage 60 VDC; 42 VAC (safety extra-low voltage)
Maximum switch current 1.0 A
Signal transmission
Transmission rate 9.6; 19.2; 45.45; 93.75; 187.5; 500 kBit/s
1.5; 3; 6; 12 Mbit/s
Setting transmission rate automatic
Bit error rate < 10
-9
Signal processing time (any input/output) 6.5 t
Bit
Retimer
Input Port 1 to 3
Signal distortion ±30 %
Bit length ± 0.12 %
Output Port 1 to 3
Mean bit length ± 0.01 %
Safety
VDE regulation VDE 0805 = EN 60950 und IEC 60950
UL/CSA approval UL 1950/CSA 950
FM approval CLASS I: DIV 2 GROUP A; B; C und D; T5
Ex approval EEx nC [L] IIC T5; T
A
: 0 °C 60 °C
Electrical port
Input/output signal RS 485 level
Input dielectric strength 10 V to +15 V
PIN assignment, port 1 in accordance with EN 50170 Part 1
Optical ports
Wavelength 660 nm 860 nm 1310 nm
Launchable optical power
in glass fiber E 10/125 –––19 dBm
in glass fiber G 50/125 ––15 dBm 17 dBm
in glass fiber G 62.5/125 ––13 dBm 17 dBm
in PCF fiber S 200/230
transmitting power Reduced –––
transmitting power Default“–17 dBm ––
in plastic fiber S 980/1000
transmitting power Reduced 9.5 dBm ––
transmitting power Default“–5 dBm ––
Receiver sensitivity 25 dBm 28 dBm 29 dBm
Receiver overload 3 dBm 3 dBm 3 dBm
7 Technical Data