Technical specifications
6.1 Technical specifications
Analog Input Module AI 4xI 2-/4-wire ST (6ES7134-6GD01-0BA1)
29 Equipment Manual, 06/2020, A5E03551866-AF
Interrupts/diagnostics/status information
• Diagnostic alarm
Yes
• Limit value alarm
No
• Monitoring the supply voltage
Yes
• Wire-break
Yes; at 4 to 20 mA
• Short-circuit
Yes; 2-wire mode: Short-circuit of the encoder
supply to ground or of an input to the encoder
• Group error
Yes
• Overflow/underflow
Yes
Diagnostics indication LED
• Monitoring of the supply voltage (PWR-
LED)
Yes; green LED
• Channel status display
Yes; green LED
• for channel diagnostics
No
• for module diagnostics
Yes; green/red LED
Potential separation channels
• between the channels
Yes; channel group-specific between 2-wire cur-
rent input group and 4-wire voltage input group
• between the channels and backplane bus
Yes
• between the channels and the power sup-
ply of the electronics
Yes; only for 4-wire transducer
Permissible potential difference
Ambient temperature during operation
• horizontal installation, min.
-30 °C
• horizontal installation, max.
60 °C
• vertical installation, min.
-30 °C
• vertical installation, max.
50 °C
Altitude during operation relating to sea level
• Installation altitude above sea level, max.
5 000 m; Restrictions for installation altitudes > 2