Technical specifications
11.14 Mobile Panel 2nd Generation F-FBs
Mobile Panels 2nd Generation
Operating Instructions, 09/2018, A5E33876626-AC
261
ACK_REI Bool Acknowledgement for reintegration
The automatic reintegration is regulated via
the F-I/O DB through this output.
F-I/O DB:
DBx0.2 = ACK_REI
GLOBAL_E_STOP Bool This output returns device-specific emergency
MP_E_STOP Word This output returns the effective-range-
specific emergency stop information for the
MP_ENABLE Word This output returns the effective-range-
specific "Acknowledgment" information for the
MP_DATA_Q Int User data of the fail-safe process image's
PIO:
DIAG Word Information about any occurring errors is
provided through this output for servicing
purposes. The value has the following
meaning:
0x0001: HMI removed
0x0002: HMI device integrated; emergency
stop and acknowledgment button are
available.
0x0004: Communication error occurred,
emergency stop activated, enabling button
deactivated
0x0008: Communication error must be
acknowledged. Emergency stop is enabled;
acknowledgement button is disabled.
0x0010: HMI device removed, integration is
being prepared.
All other values: Reserved
You can evaluate
the DIAG output in
your program.
When you call a fail-safe block, the enable input EN and enable output ENO appear
automatically.
Note the following:
● Do not connect these I/Os
● Do not supply these I/Os with "0"
● Do not evaluate these I/Os