Certification
6.2EMC and Environmental Type Tests
Description Test Levels
Signal Ports 5 kV (Failsafe Relay)
DC Power Ports 5 kV
HV Impulse
AC Power Ports 5 kV
Signal Ports 2 kV (Failsafe Relay)
DC Power Ports 1.5 kV
Dielectric Strength
AC Power Ports 2 kV
Environmental Type Tests
Test Description Test Levels Severity Levels
IEC 60068-2-1 Cold Temperature Test Ad -40 °C (-40
°F), 16 Hours
IEC 60068-2-2 Dry Heat Test Bd 85 °C (185
°F), 16 Hours
IEC 60068-2-30 Humidity (Damp
Heat, Cyclic)
Test Db 95% (Non-
Condensing),
55 °C (131
°F), 6 Cycles
IEC 60255-21-1 Vibration 2 g @ 10 to 150 Hz Class 2
IEC 60255-21-2 Shock 30 g @ 11 ms Class 2