Installation and commissioning
5.2 Installation - procedure
CP 443-1 (EX30)
Manual, 03/2019, C79000-G8976-C255-05
39
WARNING
Cable
If the cable or conduit entry point exceeds 70 °C or the branching point of conductors
exceeds 80 °C, special precautions must be taken. If the equipment is operated in an air
ambient in excess of 50 °C, only use cables with admitted maximum operating temperature
of at least 80 °C.
WARNING
Take measures to prevent transient voltage surges of more than 40% of the rated voltage.
This is the case if you only operate devices with SELV (safety extra-low voltage).
5.1.3
Notices on use in hazardous areas according to UL HazLoc
WARNING
EXPLOSION HAZARD
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-
hazardous locations only.
This equipment is suitable for use in Class I, Zone 2, Group IIC or non-hazardous locations
only.
5.2
Installation - procedure
The steps for installing the CP are explained below.
Result: The CP is installed in the rack and the interfaces have been networked.

Table of Contents

Other manuals for Siemens SIMATIC NET S7-400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET S7-400 and is the answer not in the manual?

Siemens SIMATIC NET S7-400 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET S7-400
CategoryConference System
LanguageEnglish

Related product manuals