EasyManuals Logo

Siemens SIMATIC NET Series User Manual

Siemens SIMATIC NET Series
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
SCALANCE W1788-x
1.3 General approvals
Approvals SCALANCE W1700 802.11ac
16 Reference Manual, 11/2018, C79000-G8976-C487-02
IECEx
The SIMATIC NET products meet the requirements of explosion protection according to
IECEx.
Note
Type of protection of the device
The devices are approved for various types of protection. You can find the type of protection
of your device and the IECEx certificate number on the nameplate.
Permitted types of protection
The following types of protection are possible:
nA
IECEx classification: Ex nA IIC T4 Gc
Certificate no.: DEK 14.0025X
The products meet the requirements of the following standards:
EN 60079-15 (Explosive atmospheres - Part 15: Equipment protection by type of
protection "n")
EN 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)
ec
IECEx classification: Ex ec IIC T4 Gc
Certificate no.: DEK 18.0018X
The products meet the requirements of the following standards:
EN 60079-7 (Explosive atmospheres - Part 7: Equipment protection through increased
safety "e")
EN 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)
You will find the current versions of the standards in the currently valid IECEx certificates.
E1
The device meets the requirements of the ECE R10 directive.
Test number 10 R - 057876

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET Series and is the answer not in the manual?

Siemens SIMATIC NET Series Specifications

General IconGeneral
Product TypeNetwork Card
Interface TypeEthernet
Communication ProtocolPROFINET, Ethernet/IP
Connector TypeRJ45
Operating Temperature0°C to 60°C
ProtocolsTCP/IP, UDP, SNMP
Power Supply24V DC
CertificationsCE, UL, FCC