EasyManuals Logo

Siemens SIMATIC PCS 7 Read Me

Siemens SIMATIC PCS 7
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
Information on configuration and operation
3
The blocks in the library have been designed exclusively for S7-400 automation systems.
ET 200iS, ET 200X and DP field devices cannot be operated on an H system downstream
from a Y link with PCS 7 standard blocks.
An ET 200S (IM 151-1 High Feature) and a diagnostics repeater can be supported
downstream from a Y-link only as a DP V0 slave, this must however be configured as DPV1.
You are not permitted to set the minimum cycle time of OB1 to a value other than "0".
With the CPU 410 PA SMART, the minimum scan cycle time of OB1 is permanently set to
200ms.
One-sided distributed I/Os are not supported in PCS 7.
The adjustable options "Status of supply voltage L+" and "Status of feedback voltage" are
not supported for ET 200SP server modules. If these options are not selected, a diagnostics
module is created for the server module. If these options are selected, a warning is issued
when compiling with the module driver generation and no diagnostics module is installed.
The functionality of these options cannot be used with channel blocks.
Value status is only supported for ET 200SP HA modules.
The user-defined data types (UDT) of 1 to 50 and 200 to 299 are reserved for PCS 7
Advanced Process Library and PCS 7 Basis Library .
PCS 7 Basis Library Readme V9.0 SP1 (online)
Readme, V9.0 SP1, A5E42614246-AA 9

Other manuals for Siemens SIMATIC PCS 7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS 7 and is the answer not in the manual?

Siemens SIMATIC PCS 7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS 7
CategoryControl Systems
LanguageEnglish

Related product manuals