Information on configuration and operation
3
The blocks in the library have been designed exclusively for S7-400 automation systems.
ET 200iS, ET 200X and DP field devices cannot be operated on an H system downstream
from a Y link with PCS 7 standard blocks.
An ET 200S (IM 151-1 High Feature) and a diagnostics repeater can be supported
downstream from a Y-link only as a DP V0 slave, this must however be configured as DPV1.
You are not permitted to set the minimum cycle time of OB1 to a value other than "0".
With the CPU 410 PA SMART, the minimum scan cycle time of OB1 is permanently set to
200ms.
One-sided distributed I/Os are not supported in PCS 7.
The adjustable options "Status of supply voltage L+" and "Status of feedback voltage" are
not supported for ET 200SP server modules. If these options are not selected, a diagnostics
module is created for the server module. If these options are selected, a warning is issued
when compiling with the module driver generation and no diagnostics module is installed.
The functionality of these options cannot be used with channel blocks.
Value status is only supported for ET 200SP HA modules.
The user-defined data types (UDT) of 1 to 50 and 200 to 299 are reserved for PCS 7
Advanced Process Library and PCS 7 Basis Library .
PCS 7 Basis Library Readme V9.0 SP1 (online)
Readme, V9.0 SP1, A5E42614246-AA 9