Load objects to the CPU
The table shows which modifications and which modified blocks you can download in which operating mode.
Very complex programs can prevent downloading in RUN mode. Solution approaches:
Use a memory card with sufficient capacity.
Select a CPU with sufficient work memory.
Reduce the number of modified used blocks, constants, PLC tags or data types.
You can find information about the behavior of the F-CPU for fail-safe blocks in the SIMATIC Safety Configuring and
Programming manual.
Modifications and blocks S7-300 S7-400 S7-1200
V4.0 or
higher
S7-1500 S7-1200
V1.0 - 2.1
S7-1200
V2.2 - V3.0
Modified properties of hardware
components
STOP
STOP,
constraints in
RUN
STOP STOP STOP STOP
Added hardware components
STOP
STOP,
constraints in
RUN
STOP STOP STOP STOP
New/revised text lists
(alarms)
RUN RUN - RUN - -
Load number of blocks
RUN (<17) RUN (<57) RUN (<21) RUN STOP RUN (<11)
Reset work memory (MRES)
STOP
(Reset)
STOP
(Reset)
STOP
(Reset)
STOP
(Reset)
STOP
(Reset)
STOP
(Reset)
New OB
RUN RUN STOP RUN STOP STOP
Modified OB: Code modifications,
modification of comments
RUN RUN RUN RUN STOP RUN

Other manuals for Siemens SIMATIC S7-1200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1200 and is the answer not in the manual?

Siemens SIMATIC S7-1200 Specifications

General IconGeneral
CPU TypeCPU 1211C, CPU 1212C, CPU 1214C, CPU 1215C, CPU 1217C
CommunicationPROFINET
Analog Inputs2
Analog Outputs2
Power Supply24V DC
Expansion ModulesSignal Modules (SM), Communication Modules (CM)
Programming LanguagesLAD, FBD, SCL
Dimensions90 mm x 100 mm x 75 mm
Program Memory50 KB to 150 KB (depending on model)

Related product manuals