EasyManua.ls Logo

Siemens Simatic S7-1500 - Page 102

Siemens Simatic S7-1500
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring
4.3 Terminal and block diagrams
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
102 Manual, 09/2016, A5E35306440-AB
Technical characteristics of the outputs
The following table shows an overview of the technical characteristics of the individual
outputs.
Frequency range
(period duration)
DQ0 to DQ7
DQ8 to DQ15
High-speed output
(0.1 A) activated
High-Speed output
(0.1 A) deactivated
Standard output
max. 100 kHz max. 10 kHz max. 100 Hz
max. 0.1 A
max. 0.5 A
max. 0.5 A
Switching to P potential /
sink output
Switching to P potential Switching to P potential
Accuracy of
the pulse
duration
10 to <= 100 kHz (100 to >
= 10 µs)
±100 ppm ±2 µs --- ---
100 Hz to <10 kHz (10 ms
to > 100 µs)
±100 ppm ±10 µs with
load > 0.1 A
±100 ppm ±20 µs with
load 2mA
10 to < 100 Hz (0.1 s to
> 10 ms)
±100 ppm ±100 µs with
load > 0.1 A
±100 ppm ±200 µs with
load 2mA
1 to <10 Hz (1 to > 0.1 s) ±150 ppm ±2 µs ±150 ppm ±10 µs with
load > 0.1 A
±150 ppm ±20 µs with
load 2mA
±150 ppm ±100 µs with
load > 0.1 A
±150 ppm ±200 µs with
load 2mA
0.1 to < 1 Hz (10 to >1 s) ±600 ppm ±2 µs ±600 ppm ±10 µs with
load > 0.1 A
±600 ppm ± 20 µs with
load 2mA
±600 ppm ±100 µs with
load > 0.1 A
±600 ppm ±200 µs with
load 2mA
Minimum
pulse dura-
tion
--- 2 µs 20 µs with load > 0.1 A
40 µs with load ≥ 2 mA
100 µs with load > 0.1
A
200 µs with load ≥ 2
mA

Table of Contents