EasyManua.ls Logo

Siemens Simatic S7-1500 - Page 176

Siemens Simatic S7-1500
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog value processing
C.1 Conversion method
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
176 Manual, 09/2016, A5E35306440-AB
Smoothing
The individual measured values are smoothed by filtering. The smoothing can be set in
4 levels and channel-selective in STEP 7 (TIA Portal).
Smoothing time = Smoothing (k) x configured integration time
The following figure shows the time it takes for the smoothed analog value to reach
approximately 100 % depending on the set smoothing. This is valid for all signal changes at
the analog input.
None (smoothing = 1 x integration time)
Weak (smoothing = 4 x integration time) *
Medium (smoothing = 16 x integration time) *
Strong (smoothing = 32 x integration time) *
* The smoothing time can increase by 1 x integration time.
Figure C-5 Smoothing time depending on the set smoothing level

Table of Contents