2 Requirements for Use
B−12
CP 443-1 for Industrial Ethernet / Manual Part B
Release 07/2010
C79000-G8976-C223−06
Table 2-1 CPU data relevant to use of the CP
CPU as of firmware versionOrder number of
the CPU:
6ES7...
CPU
Multiprocessing possible
Order number of
the CPU:
6ES7...
CPU
Max. number of CPs
Order number of
the CPU:
6ES7...
CPU
CPU resources for
SEND-/RECEIVE jobs
1)
Order number of
the CPU:
6ES7...
LOCK/UNLOCK
PROFINET IO
4)
CPU 416-3 PN/DP ..416−3ER05−0AB0 V5.1 +
2)
14 64 + +
CPU 416F−3 PN/DP ..416−3FR05−0AB0 as of
V5.1
+
2)
14 64 + +
CPU 417-4 ..417−4XL04−0AB0 V4.1 +
2)
14 64 + −
CPU 417-4 ..417−4XT05−0AB0 as of
V5.1
+
2)
14 64 + +
CPU 412-3H
3)
..412-3HJ14-0AB0 V4.5 +
2)
14 64 + −
CPU 414H
3)
..414-4HM14-0AB0 V4.5 +
2)
14 64 + −
CPU 414H
3)
5)
..414−4HJ04−0AB0 V4.0 +
2)
14 64 + −
CPU 417H
3)
..414-4HR14-0AB0 V4.5 +
2)
14 64 + −
CPU 417H
3)
..417−4HT14−0AB0 V4.5 +
2)
14 64 + −
CPU 417H
3)
5)
..417−4HL04−0AB0 V4.0 +
2)
14 64 + −
Legend:
+ => The feature is supported / the specified mode is possible
=> the feature is not supported / the specified the mode is not possible
1)
The calculation of the maximum number of SEND/RECEIVE calls that can be used simultaneously per CP
is described in Section 5.3.2.
2)
When using the CP as a PROFINET IO controller, multiprocessor mode is not supported, in other words,
only the process image of the assigned CPU can be distributed via the CP (Note: this does not affect
communication protocols running at the same time in multiprocessor mode).
3)
When operating with H-CPUs, the SSEND / SRECV mode on the SEND/RECV interface is not supported.
H−CPUs do not support PROFINET.
4)
The PROFINET IO mode shared device requires a CPU as of Version V5.3.
5)
When operating these H CPUs, the CP must be configured as module type CP 443−1 EX11.
2.3 Configuration
The following version of STEP 7 is required:
Table 2-2
STEP 7 version
CP 443-1 functionality
as of V5.4 + Service Pack 4 The full functionality as described in this document can be used.