02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-55
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
Setting values for configuring the setpoint processing function and ramp-function generator
Limitation at ramp-function generator output (setpoint limitation)
(see also Section 8, Sheet G136)
The effective limitations are:
Upper limit: Minimum value of P300 and the four connectors selected with P632
Lower limit: Maximum value of P301 and the four connectors selected with P633
Note: The limiting values for both the positive and negative setpoint limits can have a positive or negative sign. The negative setpoint
limit, for example, can therefore be parameterized to a positive value and the positive setpoint limit to a negative value.
P632
*
Source for variable positive limitation at ramp-function generator
output
Selection of connectors to be injected at the variable positive limitation at
the ramp-function generator output (setpoint limitation).
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P633
*
Source for variable negative limitation at ramp-function generator
output
Selection of connectors to be injected at the variable negative limitation
at the ramp-function generator output (setpoint limitation).
0 = connector K0000
...
8 = connector K0008
9 = value as set in parameter P632 ∗ (−1)
10 = connector K0010
etc.
All connector
numbers
1
Ind: 4
FS=9
Type: L2
P052 = 3
P051 = 40
Offline
P634
*
Source for limitation input at ramp-function generator output
Selection of connectors which must be added up to provide the limitation
input at the ramp-function generator output (setpoint limitation).
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 2
FS=
i001: 190
i002: 0
Type: L2
P052 = 3
P051 = 40
Offline
P635
*
FDS
Source for ramp-function generator setpoint
Selection of connector to be injected as the ramp-function generator
setpoint
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=194
Type: L2
P052 = 3
P051 = 40
Offline
P636
*
Source for reduction signal for ramp-function generator times
Selection of connector to be injected as the reduction signal for the
ramp-function generator times
i001 acts on ramp-up and ramp-down time (P303, P304)
i002 acts on lower and upper transition roundings (P305, P306)
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 2
FS=2
Type: L2
P052 = 3
P051 = 40
Offline
P637
*
BDS
Source for selection of "Ramp-function generator setting 2"
Selection of binector to control switchover to "Ramp-function generator
setting 2".
With a log. "1" signal at the binector, ramp-function generator parameter set
2 (P307 - P310) is selected. This function has a higher priority than the
ramp-up integrator function.
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline