02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-93
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U169
(2169)
*
S00
Source for input quantity for 4
th
abs.-value generator with filter FB 63
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U170
(2170)
*
S00
Signal injection mode for 4
th
abs.-value generator with filter FB 63
0 Injection of signal with correct sign
1 Injection of absolute value of signal
2 Injection of signal with sign, inverted
3 Injection of absolute value of signal, inverted
0 to 3
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
U171
(2171)
S00
Filter time for 4
th
abs.-value generator with filter FB 63
0 to 10000
[ms]
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
11.54 Processing of connectors
Only active with optional technology software S00
Averager [SW 1.8 and later] FB 16, FB 17, FB 18, FB 19
U172
(2172)
*
S00
Source for input signal
i001: 1st averager (FB 16)
i002: 2nd averager (FB 17)
i003: 3rd averager (FB 18)
i004: 4. averager (FB 19)
Settings:
0 = Connector K0000
1 = Connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
off-line
U173
(2173)
S00
Number of sampling cycles
i001: 1st averager (FB 16)
i002: 2nd averager (FB 17)
i003: 3rd averager (FB 18)
i004: 4. averager (FB 19)
1 to 100
1
Ind: 4
FS=1
Type: O2
P052 = 3
P051 = 40
on-line
11.55 Limiters, limit-value monitors
Parameters apply only if optional S00 technology software is installed
Limiters
The input quantity selected via index i001 of the 1
st
parameter is limited to the limit values selected via indices i002 and i003 and applied
to the specified connector. Violation of the limit values is signalled by means of two binectors.
U175
(2175)
*
S00
Source for input signal and limits for limiter 1 FB 65
Output = connector K9167
i001: Input signal
i002: Positive limiting value (L+)
i003: Negative limiting value (L-)
Settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 3
FS=
i001: 0
i002: 9165
i003: 9166
Type: L2
P052 = 3
P051 = 40
Offline
U176
(2176)
S00
Limit value for limiter FB 65
Applied to connector K9165
-199.99 to 199.99
[%]
0.01%
Ind: None
FS=100.00
Type: I2
P052 = 3
P051 = 40
Offline