02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-95
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U192
(2192)
S00
Hysteresis for 2
nd
limit-value monitor with filtering FB 71
0.00 to 199.99
[%]
0.01%
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Offline
U193
(2193)
*
S00
Source for input signal (A) and operating point (B) for FB 72
3
rd
limit-value monitor with filtering
i001: Input signal
i002: Operating point
Settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 2
FS=
i001: 0
i002: 9185
Type: L2
P052 = 3
P051 = 40
Offline
U194
(2194)
S00
Settable operating point for limit-value monitor FB 72
Applied to connector K9185
-200.00 to 199.99
[%]
0.01%
Ind: None
FS=0.00
Type: I2
P052 = 3
P051 = 40
Offline
U195
(2195)
S00
Filter time for 3
rd
limit-value monitor with filtering FB 72
0 to 10000
[ms]
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
U196
(2196)
S00
Hysteresis for 3
rd
limit-value monitor with filtering FB 72
0.00 to 199.99
[%]
0.01%
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Offline
Limit-value monitors without filtering
U197
(2197)
*
S00
Source for input signal (A) and operating point (B) for FB 73
1
st
limit-value monitor without filtering
i001: Input signal
i002: Operating point
Settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 2
FS=
i001: 0
i002: 9186
Type: L2
P052 = 3
P051 = 40
Offline
U198
(2198)
S00
Settable operating point for limit-value monitor FB 73
Applied to connector K9186
-200.00 to 199.99
[%]
0.01%
Ind: None
FS=0.00
Type: I2
P052 = 3
P051 = 40
Offline
U199
(2199)
S00
Hysteresis for 1
st
limit-value monitor without filtering FB 73
0.00 to 199.99
[%]
0.01%
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Offline
U200
(2200)
*
S00
Source for input signal (A) and operating point (B) for FB 74
2
nd
limit-value monitor without filtering
i001: Input signal
i002: Operating point
Settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 2
FS=
i001: 0
i002: 9187
Type: L2
P052 = 3
P051 = 40
Offline
U201
(2201)
S00
Settable operating point for limit-value monitor FB 74
Applied to connector K9187
-200.00 to 199.99
[%]
0.01%
Ind: None
FS=0.00
Type: I2
P052 = 3
P051 = 40
Offline
U202
(2202)
S00
Hysteresis for 2
nd
limit-value monitor without filtering FB 74
0.00 to 199.99
[%]
0.01%
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Offline