Error scenarios
In the event of an error, a diagnostic buffer entry signals that it was not possible to determine
whether a module has been replaced.
Possible reasons are:
The serial number of the device cannot be determined.
The serial number saved on the CompactFlash card cannot be determined, for example,
due to a corrupt file system.
The controller has not powered up.
The new serial number could not be transferred to the CompactFlash card, for example,
due to a corrupt file system.
Restart after reloading
The system variable device.startupData.operationMode is used to define whether the
SIMOTION D4x5-2 control unit goes into the RUN state or the last operating state after a
power-on/restart.
Possible values of device.startupData.operationMode:
LAST_OPERATION_MODE [0] (default setting)
RUN [1]
With LAST_OPERATION_MODE [0], the module remains in the STOP state after reloading
the non-volatile SIMOTION data and must be switched manually to the RUN state with
SCOUT, IT DIAG or the mode selector switch .
With RUN [1], the module goes automatically into the RUN state after reloading.
SINAMICS module replacement
A module replacement is detected as of SINAMICS V4.5.
For the SINAMICS Integrated, CX32-2 and SINAMICS S120 CU310-2/CU320-2, a module
replacement is also identified via the serial number. Non-volatile SINAMICS data (NVRAM
data) backed up previously via the CU parameter p7775 on the CompactFlash card, is then
automatically transferred to the control unit.

Table of Contents

Other manuals for Siemens SIMOTION D435-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION D435-2 and is the answer not in the manual?

Siemens SIMOTION D435-2 Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION D435-2
CategoryControl Unit
LanguageEnglish

Related product manuals