Installation
3.12 Default settings of inputs and outputs (CU240D-2)
SINAMICS G120D converter
Getting Started, 07/2016, FW V4.7 SP6, A5E38556189B AA
53
Default setting 8: "MOP with Basic Safety"
DO 0: p0730, DO 1: p0731
DI 0: r0722.0, …, DI 5: r0722.5
Motorized potentiometer, setpoint after the ramp-function generator r1050
Speed setpoint (main setpoint): p1070[0] = 1050
Default setting 9: "Standard I/O with MOP"
DO 0: p0730, DO 1: p0731
DI 0: r0722.0, …, DI 3: r0722.3
Motorized potentiometer, setpoint after the ramp-function generator r1050
Speed setpoint (main setpoint): p1070[0] = 1050