Extinguisher system
14
Building Technologies
Fire Safety
Deactivating the extinguisher system
Pull out the interlock (1).
Turn the ball valve through 90° (2).
The ball valve is closed, and the extinguisher system is
deactivated.
The communication interface indicates the inactive state as follows:
Operation (green)
Extinguisher system inactive
(yellow)
Acoustic signal
Every 10 minutes for 6 seconds.
Flashing light
Every 10 minutes for 6 seconds.
The Lifdes
TM
pneumatic detection tube is still under pressure. If there is damage to the tube,
however, the loss of pressure will not initiate an extinguishing procedure.
Reactivating the extinguisher system
Warning!
The activation of the extinguisher system may only be carried out by authorised personnel. The
latter is responsible for ensuring that the extinguisher system is activated again before the start
of the production.
Important!
Check the pressure in the pneumatic Lifdes
TM
detection tube. A pressure gauge (manometer) is
mounted on the manual start.
1
2