Extinguisher system
13
Building Technologies
A54475-A1-A2_EN_05.docx
Fire Safety
01.2018
Checking the extinguisher system
Warning!
The activation of the extinguisher system may only be carried out by authorised personnel.
The ball valve must point parallel to the tube direction.
It is opened, and the extinguisher system is activated.
The key on the Communication Interface must be pulled out.
The Communication Interface indicates the active state as follows:
Operation (green)
The system is now in operation.
3.3 Deactivating/activating the system
Danger to life!
Before you or any other person enter the protected area of the machine tool to carry out
maintenance work, the extinguisher system must first be deactivated by authorised personnel! If
the pneumatic Lifdes
TM
detection tube is accidentally damaged, carbon dioxide (CO
2
) will flow
out of the extinguisher system and you must protect yourself and other persons, as this is
deadly in high doses!
Warning!
The activation and deactivation of the extinguisher system may only be carried out by
authorised personnel. They are responsible for ensuring that the extinguisher system is
reactivated again before the start of the production.