PLC alarms
11/2006 Overview of Alarms
2-815
© Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
400157 Delete DB 57 in the PLC and restart
Definitions: The DB created by the basic program and the existing DB differ in size.
Reaction: Alarm display.
Remedy: Displayed DB must be deleted via STEP7. Possibly max. program size of the user program exceeded.
Program
Continuation:
Internal
400158 Delete DB 58 in the PLC and restart
Definitions: The DB created by the basic program and the existing DB differ in size.
Reaction: Alarm display.
Remedy: Displayed DB must be deleted via STEP7. Possibly max. program size of the user program exceeded.
Program
Continuation:
Internal
400159 Delete DB 59 in the PLC and restart
Definitions: The DB created by the basic program and the existing DB differ in size.
Reaction: Alarm display.
Remedy: Displayed DB must be deleted via STEP7. Possibly max. program size of the user program exceeded.
Program
Continuation:
Internal
400160 Delete DB 60 in the PLC and restart
Definitions: The DB created by the basic program and the existing DB differ in size.
Reaction: Alarm display.
Remedy: Displayed DB must be deleted via STEP7. Possibly max. program size of the user program exceeded.
Program
Continuation:
Internal
400161 Delete DB 61 in the PLC and restart
Definitions: The DB created by the basic program and the existing DB differ in size.
Reaction: Alarm display.
Remedy: Displayed DB must be deleted via STEP7. Possibly max. program size of the user program exceeded.
Program
Continuation:
Internal
400171 Delete DB 71 in the PLC and restart
Definitions: The DB created by the basic program and the existing DB differ in size.
Reaction: Alarm display.
Remedy: Displayed DB must be deleted via STEP7. Possibly max. program size of the user program exceeded.
Program
Continuation:
Internal
400172 Delete DB 72 in the PLC and restart
Definitions: --
Reaction: Alarm display.
Remedy: See the machine manufacturer's information.
Program
Continuation:
Internal