Set-up
12
Building Technologies
Fire Safety & Security Products 06.2009
4 Set-up
The InfoPoint has integrated software for browsing the reservation functions in the
Segment Controller. It needs only to be set-up with the IP-address for the SR35i
Segment Controller in order to gain access to these functions.
In addition, the factory settings listed in the table on the next page will be used by
default. However, these parameters must be decided together with the IT-manager
and must be coordinated with the overall host computer network.
If there is a DHCP server (Dynamic Host Configuration Protocol) available in the
network, the InfoPoint networking parameters (such as IP address, Netmask and
Gateway) could be configured automatically. (This requires that the parameter
DHCP be set to YES).
4.1 Factory settings – and to reset
The first time you power up the InfoPoint, it has some factory set parameters ac-
cording to the table below. To edit any of these - see Change settings.
To reset the factory settings:
1. Disconnect the power supply – or restart.
2. Press and hold the marked button (see figure). Hold it down until you hear
three beeps. z
3. Using the minus button furthest down, go down to the Factory settings and
press YES.
4. A warning message is displayed and you have to choose whether to proceed
(YES) - or not (NO).
Factory settings:
DHCP (NO or YES) ÆNO
- DHCP NO Æ Own IP address: 10.1.200.200 For InfoPoint
- DHCP NO Æ Netmask: 255.255.255.0 For InfoPoint
- DHCP NO Æ Gateway: 10.1.200.1 For InfoPoint
DNS Server 1 0.0.0.0 Name Server
DNS Server 2 0.0.0.0 Name Server
Server IP-address 10.1.200.101 IP-address for SR35i. Do not
enter a dot after the last digit!
If using names instead, the IP for
the DNS above must be set.
Server Path /infopoint/ Search path to the CF8 memory
card of the SR35i.
Start page index.iml Start page SR35i
DynDNS Server members.dyndns.org DHCP function
DynDNS Username <empty> DHCP function
DynDNS Password <empty> DHCP function
DynDNS Hostname <empty> DHCP function