$SSHQGL[5:
9

&*&
Annunciations 7RW600 for PC, LC-display and binary inputs/outputs
²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²
FNo. - Function number of annunciation
Op/Ft - Operation/Fault annunciation
C/CG: Coming/Coming and Going annunciation
M : Measurand
I - can be marshalled to binary input
O - can be marshalled to binary output (LED, signal/trip relay)
¿©©©©§©©©©©©©©§©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©§©©§©©§©§©¤
FNo.Text Meaning OpFtIO
¨©©©©ª©©©©©©©©ª©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©ª©©ª©©ª©ª©
1not all.Not allocated IO
3>Ti.syn >Time synchronization IO
5>LED r. >Reset LED indicators IO
52operat. Any protection operative CG O
60LED res LED Reset C O
83SigTest For internal use only O
110ANNlost Annunciations lost (buffer overflow) C O
111PCannLT Annunciations for PC lost C O
113TAGlost Fault tag lost O
115ANNovfl Fault annunciation buffer overflow C O
203REC del Fault recording data deleted C O
301Sys.Flt Fault in the power system C C O
302FAULT Flt. event w. consecutive no. C C O
501FT det General fault detection of device CG O
511DEV.Trp General trip of device C O
527f= Interrupted frequency f= C O
528U= Interrupted voltage U= C O
529Ux= Interrupted voltage Ux= C O
694f= Frequency f [Hz] = M O
765U/f= Overflux (U/Un) / (f/fn) M O
907Up= Positive sequence voltage M O
937- Frequency f [Hz] = (only LSA) M O
968U= Voltage U M O
969Ux= Voltage Ux M O
1157>CBclo >Circuit breaker closed CG IO
1174CBtest Circuit breaker test in progress CG O
1185CBtpTST Circuit breaker test: Trip 3pole CG O
5203>Frq bl >Block frequency protection IO
5206>f1 blk >Block frequency prot. f1 stage CG IO
5207>f2 blk >Block frequency prot. f2 stage CG IO
5208>f3 blk >Block frequency prot. f3 stage CG IO
5209>f4 blk >Block frequency prot. f4 stage CG IO
5211Frq off Frequency protection is switched off CG O
5212Frq bl Frequency protection is blocked CG O
5213Frq act Frequency protection is active CG O
5214Uf< bl Frequency protection blocked by U< CG O
5232f1 Flt. Frequency protection: Fault stage f1 CG O
5233f2 Flt. Frequency protection: Fault stage f2 CG O
5234f3 Flt. Frequency protection: Fault stage f3 CG O
5235f4 Flt. Frequency protection: Fault stage f4 CG O
5236f1 Trip Frequency protection: Trip stage f1 C O
5237f2 Trip Frequency protection: Trip stage f2 C O
5238f3 Trip Frequency protection: Trip stage f3 C O
5239f4 Trip Frequency protection: Trip stage f4 C O
5353>U/f bl >Block overexcitation protection IO
5357>RM U/f >Reset memory of thermal replica U/f CG IO
5361U/f off Overexcitation prot. is swiched off CG O
5362U/f blk Overexcitation prot. is blocked CG O
¥©©©©¦©©©©©©©©¦©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©¦©©¦©©¦©¦©¾