-ETHOD OF OPERATION3*
6
#
' #

 5NBALANCED LOAD PROTECTION
4HE UNIT IS EQUIPPED WITH AN UNBALANCED LOAD PRO
TECTION WHICH IS ADVANTAGEOUS FOR PROTECTION OF MO
TORS WHICH ARE SWITCHED BY VACUUM CONTACTORS WITH
ASSOCIATED FUSES 7HEN RUNNING ON SINGLE PHASE THE
MOTORS DEVELOP SMALL AND PULSATING TORQUES SO THAT
WITH UNCHANGED TORQUE LOAD THE MOTOR WILL BE QUICK
LY THERMALLY OVERLOADED &URTHERMORE THERMAL OVER
LOADING OF THE MOTOR MAY ARISE BY UNSYMMETRICAL
SYSTEM VOLTAGE %VEN SMALL UNBALANCED SYSTEM VOLT
AGES MAY LEAD TO LARGE SLIP LOAD CURRENTS BECAUSE OF
THE SMALL NEGATIVE SEQUENCE REACTANCES
4HE UNBALANCED LOAD PROTECTION DETECTS ADDITIONAL
LY INTERRUPTIONS SHORT
CIRCUITS AND SWOPPED
PHASE CONNECTIONS OF THE CURRENT TRANSFORMER CIR
CUITS 3INGLE
PHASE AND TWO PHASE SHORT CIRCUITS
CAN BE DETECTED EVEN WHEN THE FAULT CURRENT IS TOO
SMALL TO BE DETECTED BY THE OVERCURRENT TIME PROTEC
TION
)N THE UNBALANCED LOAD PROTECTION OF THE 3* THE
FUNDAMENTAL WAVE OF THE PHASE CURRENTS IS FILTERED
OUT AND SEPARATED INTO SYMMETRICAL COMPONENTS
NEGATIVE SEQUENCE )
AND POSITIVE SEQUENCE )

4HE RATIO )
)
.
)
.
RATED RELAY CURRENT IS EVALUATED
FOR UNBALANCED LOAD DETECTION
4HE UNBALANCED LOAD PROTECTION HAS TWO
STAGE DE
SIGN )F THE FIRST ADJUSTABLE THRESHOLD )
IS REACHED
TIMER 4
)
IS STARTED THE SECOND ADJUSTABLE THRESH
OLD )
 STARTS THE TIMER 4
)
SEE &IGURE 
7HEN THE ASSOCIATED TIME HAS ELAPSED TRIP COM
MAND IS ISSUED
&ILTERING OF THE NEGATIVE SEQUENCE CURRENT IS POSSI
BLE AS LONG AS THE HIGHEST OF THE THREE PHASE CURRENTS
IS AT LEAST  TIMES RATED CURRENT OF THE RELAY AND ALL
PHASE CURRENTS ARE SMALLER THAN TIMES RATED CUR
RENT
&IGURE  SHOWS THE LOGIC DIAGRAM OF THE UNBAL
ANCED LOAD PROTECTION
T
4
)
4
)
)
)
 )
TRIP STAGE )
TRIP STAGE )

4RIP AREA
&IGURE  4RIP TIME CHARACTERISTIC OF THE UNBALANCED LOAD PROTECTION
ONLY FOR MODEL 3*J JJJJ JJJJ