-ETHOD OF OPERATION3*
6

#
' #
 (IGHLY SENSITIVE EARTH FAULT PROTECTION
4HE HIGHLY SENSITIVE EARTH FAULT PROTECTION CAN BE
USED IN ISOLATED OR ARC COMPENSATED NETWORKS TO DE
TECT AN EARTH FAULT TO DETERMINE THE EARTH FAULTED
PHASE AND TO DISCRIMINATE THE EARTH FAULT DIRECTION )N
EFFECTIVELY GROUNDED OR LOW
IMPEDANCE EARTHED
NETWORKS DETECTION OF HIGH
RESISTANCE EARTH FAULTS
WITH VERY SMALL FAULT CURRENTS IS POSSIBLE )T CAN BE
DELAYED AND RESULT IN ANNUNCIATION OR ALSO IN A TRIP
"ECAUSE OF ITS HIGH SENSITIVITY IT IS NOT SUITED FOR DE
TECTION OF HIGHER EARTH FAULT CURRENTS FROM ! AND
ABOVE AT THE RELAY TERMINALS FOR HIGH
SENSITIVITY
EARTH FAULT PROTECTION &OR THOSE APPLICATIONS USE
THE OVERCURRENT TIME PROTECTION FOR EARTH CURRENTS AS
DESCRIBED IN 3ECTIONS  AND 
 6OLTAGE STAGES
4HE EARTH FAULT PROTECTION FUNCTION COMPRISES THE
EARTH FAULT DETECTION BY MONITORING THE DISPLACEMENT
VOLTAGE 5
%
AND THE RECOGNITION OF THE EARTH
FAULTED PHASE 4HE DISPLACEMENT VOLTAGE MAY BE
CONNECTED DIRECTLY TO THE RELAY TERMINALS OR MAY BE
CALCULATED FROM THE SUM OF THE PHASE
TO EARTH
VOLTAGES )N THE LATTER CASE THE DISPLACEMENT VOLTAGE
CAN ONLY BE DETECTED WHEN THE RELAY IS CONNECTED TO
THREE PHASE
EARTH VOLTAGE TRANSFORMERS THE STAR
POINT OF WHICH IS EARTHED
)F THE RELAY IS CONNECTED TO PHASE
TO PHASE VOLT
AGES EARTH FAULT DETECTION IS NOT POSSIBLE AS THE DIS
PLACEMENT VOLTAGE CANNOT BE CALCULATED 4HE RELAY
IS INFORMED ABOUT THE VT CONNECTIONS DURING CONFIG
URATION
4HE DISPLACEMENT VOLTAGE 5
%
INITIATES EARTH FAULT DE
TECTION AND IS ONE CONDITION FOR RELEASE OF DIRECTIONAL
DETERMINATION ACCORDING TO 3ECTION  5
%
MEANS
THE VOLTAGE AT THE INPUT OF THE DEVICE WITH OPEN DELTA
64 IF THIS INPUT IS NOT USED THE RELAY THEN CALCULATES
5
%
o | 5
5
,
5
,
5
,
o
)N ORDER TO ENSURE MEASUREMENT OF STABLE VALUES
THE EARTH FAULT DETECTION IS DELAYED UNTIL SECOND
ADJUSTABLE AFTER INCEPTION OF VOLTAGE DISPLACEMENT
!FTER RECOGNITION OF DISPLACED VOLTAGE CONDITIONS THE
FIRST OBJECTIVE OF THE DEVICE IS SELECTIVE DETECTION OF
THE EARTH
FAULTED PHASE IF POSSIBLE &OR THIS PUR
POSE THE INDIVIDUAL PHASE
TO EARTH VOLTAGES ARE
MEASURED 4HE AFFECTED PHASE IS THE ONE IN WHICH
THE VOLTAGE IS BELOW THE SETTABLE THRESHOLD 5
PH
WHEN SIMULTANEOUSLY THE OTHER TWO VOLTAGES EXCEED
AN EQUALLY SETTABLE MAXIMUM THRESHOLD 5
PH

0ICK
UP BY THE DISPLACEMENT VOLTAGE CAN BE USED
FOR TIME DELAYED TRIP COMMAND .OTE THAT THE TOTAL
COMMAND TIME IS COMPOSED OF THE INHERENT MEASUR
ING TIME APPROXIMATELY  MS PLUS PICK
UP DELAY
PLUS TRIP DELAY TIME
4HE LOGIC DIAGRAM OF THE VOLTAGE STAGES OF EARTH FAULT
PROTECTION IS SHOWN IN &IGURE 
www . ElectricalPartManuals . com