EasyManua.ls Logo

Siemens SIPROTEC 7SJ531 - Page 86

Siemens SIPROTEC 7SJ531
362 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-ETHOD OF OPERATION3*
6
#
' #

%VALUATION OF THE MEASURED VALUES OCCURS AFTER THE
FAULT HAS BEEN CLEARED &ROM THE STORED AND FILTERED
VALUES AT LEAST THREE RESULTANT PAIRS FOR 2 AND 8 ARE
DETERMINED )F LESS THAN THREE RESULTANT PAIRS ARE
AVAILABLE NO FAULT LOCATION IS GIVEN &ROM THE RESUL
TANT PAIRS AVERAGE VALUE AND STANDARD DEVIATION ARE
CALCULATED !FTER ELIMINATION OF
EXCEPTIONS WHICH
ARE RECOGNIZED BY THEIR EXCESSIVE DIFFERENCE FROM
THE STANDARD DEVIATION ANOTHER AVERAGE IS AGAIN CAL
CULATED FOR 8 4HIS AVERAGE IS TAKEN AS FAULT REAC
TANCE
!S A RESULT OF THE FAULT LOCATION CALCULATION THE FOLLOW
ING OUTPUTS ARE GIVEN
THE SHORT CIRCUIT LOOP FROM WHICH THE FAULT REAC
TANCE IS DETERMINED
THE REACTANCE PER PHASE IN /HMS SECONDARY
THE FAULT DISTANCE IN KM OR MILES LINE LENGTH PRO
PORTIONAL TO THE REACTANCE CALCULATED ON THE BASIS
OF THE SET UNIT REACTANCE OF THE LINE
.OTE #ALCULATION OF THE DISTANCE IN KM OR MILES CAN
ONLY BE APPLICABLE TO HOMOGENEOUS LINE LENGTHS
"UT IF THE LINE IS MADE UP OF SECTIONS WITH DIFFERING
REACTANCE VALUES EG OVERHEAD LINE
CABLE COMBI
NATIONS THE DISTANCE TO FAULT CAN STILL BE CALCULATED
MANUALLY FROM THE REACTANCE DETERMINED BY THE FAULT
LOCATION IF THE LINE CHARACTERISTICS ARE KNOWN
 #IRCUIT BREAKER FAILURE PROTECTION
4HE CIRCUIT BREAKER FAILURE PROTECTION MONITORS THE
CORRECT OPENING OF THE ASSOCIATED CIRCUIT BREAKER
&OR THIS PURPOSE TWO CRITERIA ARE AVAILABLE
CHECK WHETHER THE CURRENT BECOMES ZERO AFTER A
TRIP COMMAND IS GIVEN
MONITOR THE CIRCUIT BREAKER S AUXILIARY CONTACTS
4HE CRITERIA WHICH SHALL CAUSE PICK
UP ARE SELECT
ABLE AND DEPEND ALSO ON THE PROTECTION FUNCTION
WHICH HAS GIVEN THE TRIP COMMAND 7HEN A TRIP COM
MAND IS GIVEN WITHOUT SHORT
CIRCUIT CURRENT EG BY
A VOLTAGE PROTECTION THEN THE CURRENT IS NOT A RELIABLE
CRITERION FOR THE CIRCUIT BREAKER
S REACTION 4HEREFORE
THE PICK
UP CAN BE MADE DEPENDENT ON THE AUXILIA
RY CONTACT CRITERION ALONE )F HOWEVER THE CURRENT CRI
TERION IS FULFILLED IE THE CURRENT REMAINS ABOVE A SET
TABLE THRESHOLD THEN THE TRIP COMMANDS ARE NOT DIS
TINGUISHED AS TO THEIR ORIGINATING PROTECTION FUNCTION
)N THIS CASE A CIRCUIT BREAKER FAILURE IS ALWAYS AS
SUMED
4HERE ARE THREE DIFFERENT SOURCES FOR AN INITIATION OF
THE CIRCUIT BREAKER FAILURE PROTECTION
INTERNAL PROTECTION FUNCTIONS IN THE 3*
EXTERNAL STARTING SIGNALS VIA BINARY INPUT
CONTROL COMMAND VIA OPERATING PANEL OR INTER
FACE
%ACH OF THESE SOURCES CAN BE SWITCHED ON OR OFF SEP
ARATELY AND CREATES DIFFERENT ANNUNCIATIONS
5PON DETECTION OF A CIRCUIT BREAKER FAILURE THE CORRE
SPONDING ALARM IS GIVEN AND FAULT CLEARING IS INITIATED
VIA THE SURROUNDING CIRCUIT BREAKERS AFTER A SETTABLE
TIME DELAY 4HIS CAN BE ACHIEVED BY MEANS OF ONE OF
THE MARSHALLABLE TRIP RELAYS A MARSHALLABLE ALARM
RELAY CAN BE USED AS WELL BECAUSE IN MANY CASES
AUXILIARY RELAYS WITH HIGH
DUTY CONTACTS ARE USED FOR
CONTACT MULTIPLICATION SWITCHING CAPACITY
&IGURE  SHOWS THE LOGIC DIAGRAM OF THE CIRCUIT
BREAKER FAILURE PROTECTION 4HE COMPLETE CIRCUIT
BREAKER FAILURE PROTECTION CAN BE SWITCHED ON OR OFF
VIA PARAMETERS AND BINARY INPUTS AS WELL AS DYNAMI
CALLY BLOCKED VIA BINARY INPUTS
%ACH OF THE THREE SOURCES CREATES A PICK
UP ANNUN
CIATION OF ITS OWN STARTS A TIME DELAY OF ITS OWN AND
FORMS A TRIP COMMAND OF ITS OWN 4HE PARAMETER VAL
UES FOR CURRENT THRESHOLD AND TIME DELAY ARE COM
MON
)N CASE THAT ONE OF THE CRITERIA CURRENT VALUE AUXILIA
RY CONTACT WHICH LED TO THE PICK
UP BECOMES IN
VALID DURING THE RUNNING TIME DELAY THE PICK
UP RE
SETS AND NO TRIP COMMAND IS CREATED BY THE CIRCUIT
BREAKER FAILURE PROTECTION
www . ElectricalPartManuals . com

Related product manuals