PROFIBUS Communication modules
23
SIPROTEC PROFIBUS-DP - Communication profile
C53000-L1840-B001-03
OLMMod OLM operating mode which is parameterized for the fibre-optical communication mod-
ule (ref. to chap. 2.1.2).
Redundant optical ring:
OLMMod: Redundancy
Line or Star topology with optical fibre link monitoring
OLMMod: L/S w Supv.
Line or Star topology without optical fibre link monitoring
OLMMod: Line/Star
OLMNWS Optical network size which is parameterized for the fibre-optical communication mod-
ule (ref. to chap. 2.1.2).
This parameter only is relevant if OLM V2 mode is selected:
OLMNWS: Standard
or
OLMNWS: Extended
In OLM V3 mode it is always displayed:
OLMNWS: -