SIRIUS
3UG4625
3UL23
DE
Überwachungsrelais zur
Fehlerstromüberwachung mit Wandler
Originalbetriebsanleitung
EN
Monitoring relay for
residual current monitoring with transformer
Original Operating Instructions
EL
Ρελέ ελέγχου για τον έλεγχο του
ρεύματος διαρροής με μετατροπέα
Πρωτότυπες οδηγίες χρήσης
PL
Przekaźnik monitorujący do
prądu uszkodzeniowego z przekształtnikiem
Oryginalna instrukcja obsługi
FR
Relais de surveillance de
courant de défaut avec transformateur
Instructions de service originales
ET
Trafoga kontrollrelee
rikkevooluseireks
Originaal-kasutusjuhend
RO
Releu de monitorizare pentru
monitorizarea curenţilor reziduali, cu convertizor
Instrucţiuni originale de utilizare
ES
Relé de monitoreo de
corriente diferencial con transformador
Instructivo original
FI
Valvontarele vikavirran
valvontaan muuntimella
Alkuperäinen käyttöohje
SK
Kontrolné relé na
monitorovanie chybného prúdu s meničom
Originálny návod na obsluhu
IT
Relè di controllo della corrente
di guasto con trasformatore differenziale
Istruzioni operative originali
HR
Relej za nadzor struje
kvara s pretvaračem
Originalne upute za uporabu
SL
Nadzorni rele za
nadzor okvarnega toka s pretvornikom
Originalno navodilo za obratovanje
PT
Relé de supervisão para o monitoramento
da corrente residual com transdutor
Instruções de Serviço Originais
HU
Ellenőrző jelfogó
hibaáram-felügyelethez átalakítóval
Eredeti üzemeltetési útmutató
SV
Övervakningsrelä för
felströmövervakning med omformare
Originalbruksanvisning
BG
Контролно реле с трансформатор за
наблюдение за остатъчни напрежения
Оригинално ръководство за експлоатация
LT
Kontrolinė relė liekamosios
srovės kontrolei su keitikliu
Originali eksploatacijos instrukcija
TR
Kaçak akım denetimi için
dönüştürücülü denetleme rölesi
Orijinal İşletme Kılavuzu
CS
Dohlížecí relé pro monitorování
svodového proudu s převodníkem
Originální návod k obsluze
LV
Kontroles relejs ar pārveidotāju
bojājuma strāvas kontrolei
Oriģinālā lietošanas pamācība
РУ
Контрольное реле мониторинга тока
утечки c преобразователем
Оригинальное руководство по эксплуатации
DA
Overvågningsrelæ til
fejlstrømsovervågning med omformer
Original brugsanvisning
NL
Controlerelais voor
lekstroombewaking met omzetter
Originele handleiding
中文
带互感器的用于监控故障电流的监控继电器
原始操作说明
NEB927022310000/RS-AC/003 Last update: 27 January 2016
3ZX1012-0UG40-0AA0
SIEMENS AG Telephone: +49 (911) 895-5900 (8°° - 17°° CET)
http://support.industry.siemens.com
3ZX1012-0UG40-0AB0
Technical Assistance Fax: +49 (911) 895-5907
Breslauer Str. 5 E-mail: technical-assistance@siemens.com
D-90766 Fürth Internet: www.siemens.com/sirius/technical-assistance
s
3UG4625-1CW30
3UG4625-2CW30
Question and Answer IconNeed help?

Do you have a question about the Siemens SIRIUS 3UG4625 and is the answer not in the manual?

Overview

This document describes the Siemens SIRIUS 3UG4625 and 3UL23 monitoring relays, designed for residual current monitoring with a transformer. The manual provides original operating instructions in multiple languages, including English.

Function Description

The 3UG4625 and 3UL23 devices are monitoring relays used for detecting residual currents in electrical systems. They operate in conjunction with external current transformers (3UL23 series) to measure and evaluate fault currents. The relays are designed to trip when the monitored residual current exceeds a set threshold, providing protection against electrical faults and ensuring system safety.

The relays offer various operational modes and settings, including:

  • Threshold Monitoring: The primary function is to monitor the residual current against a user-defined threshold (IΔ).
  • Time Delay: Adjustable time delays can be configured for both tripping (onDel) and reset (offDel) to prevent nuisance tripping from transient events.
  • Memory Function: The device can be configured with or without a memory function (Mem). When enabled, the relay retains its tripped state even after the fault condition clears, requiring a manual reset.
  • Hysteresis: A configurable hysteresis (Hyst) is available to prevent rapid switching when the residual current hovers around the set threshold. This is typically set as a percentage of the threshold.
  • Normally Open/Normally Closed (NO/NC) Output: The relay provides a configurable output contact (NO or NC) to interface with control systems or signaling devices.
  • Initialization (Init): The device can be initialized to a known state, with options for "ERR" (error) or "OK" (normal operation) depending on the memory setting.

The operational diagrams illustrate the relay's behavior under different conditions:

  • Mem = no; Init = ERR/OK: Shows the relay's response to residual current changes without the memory function, with different initial states. The relay trips when I > IΔ and resets when I < IΔ minus hysteresis.
  • Mem = yes; Init = ERR/OK: Demonstrates the relay's behavior with the memory function enabled. Once tripped (I > IΔ), the relay remains in the tripped state until manually reset, even if the residual current drops below the threshold.

Important Technical Specifications

Device Models:

  • 3UG4625-1CW30
  • 3UG4625-2CW30

Wiring Terminals:

  • Control Supply Voltage (A1+, A2-): The operating voltage for the relay.
  • Current Transformer Inputs (C1, C2): Connections for the external current transformer.
  • Output Contacts (11, 12, 14, 21, 22, 24): Configurable relay outputs.

Connection Data (3UG4625-1CW30):

  • Screw Type: PZ2 (Ø 5...6 mm)
  • Torque: 0.8...1.2 Nm (7 to 10.3 lb in)
  • Solid Wire: 1 x (0.5...4) mm², 2 x (0.5...2.5) mm²
  • Fine-Stranded Wire: 1 x (0.5...2.5) mm², 2 x (0.5...1.5) mm²
  • AWG: 2 x (20 to 14)

Connection Data (3UG4625-2CW30):

  • Screw Type: Ø 3.0 x 0.5 [mm]
  • Solid Wire: 2 x (0.25...1.5) mm²
  • Fine-Stranded Wire: 2 x (0.25...1.5) mm²
  • AWG: 2 x (24 to 16)

Current Transformers (3UL23 series):

  • Models: 3UL2302-1A, 3UL2303-1A, 3UL2304-1A, 3UL2305-1A, 3UL2306-1A, 3UL2307-1A
  • Mounting: Can be mounted on a DIN rail or directly to a panel.
  • Connection Data (3UL230.-1A):
    • Screw Type: PZ2
    • Torque: 0.5 Nm / 0.6 Nm (4.4 lb in / 5.3 lb in)
    • Screw Diameter: Ø 3.0
    • Solid Wire: 1 x (0.5...2.5) mm²
    • Fine-Stranded Wire: 1 x (0.5...1.5) mm²
  • Connection Data (3UL2307-1A):
    • Screw Type: PZ2
    • Torque: 0.5 Nm (4.4 lb in)
    • Screw Diameter: Ø 4.5
    • Solid Wire: 1 x (0.75...4) mm²
    • Fine-Stranded Wire: 1 x (0.75...2.5) mm²

Dimensions (approximate, in mm):

  • 3UG4625-1CW30: a=65, b=36, c=82.6, d=92.2, e=101.6
  • 3UG4625-2CW30: a=--, b=--, c=84.4, d=93.9, e=103.4
  • Overall Device Dimensions: 22.5 mm width, 110.5 mm height (including terminals), 87.2 mm depth.

Usage Features

  • Easy Installation: The relays are designed for DIN rail mounting (3RP1902, 3RP1903) or direct panel mounting, offering flexibility in installation. The current transformers can also be mounted on DIN rails or directly.
  • User-Friendly Configuration: The front panel features a display and push buttons for setting parameters such as residual current threshold (IΔ), time delays (onDel, Del), hysteresis (Hyst), and memory function (Mem).
  • Status Indication: LEDs on the front panel provide clear status indications:
    • "OK" (green): Normal operation.
    • "I!" (red, flashing): Residual current exceeds threshold, but within delay time.
    • "I!" (red, steady): Residual current exceeds threshold and relay has tripped.
    • "IΔ" (yellow): Indicates the set residual current threshold.
  • Test/Reset Functionality: A dedicated button allows for testing the relay's function and resetting it after a trip, especially when the memory function is active.
  • Current Transformer Integration: The relays are specifically designed to work with the 3UL23 series current transformers, which are available in various sizes to accommodate different conductor diameters.
  • Safety: The device is intended for use in applications requiring residual current monitoring for protection against electric shock and fire hazards. Installation and maintenance must be performed by authorized electricians to ensure safety.

Maintenance Features

  • Robust Design: Siemens SIRIUS devices are known for their robust construction, contributing to a long service life and minimal maintenance requirements.
  • Clear Wiring Diagrams: The provided wiring diagrams facilitate correct installation and troubleshooting.
  • Screw Terminals: The use of screw terminals allows for secure and reliable electrical connections, which can be easily inspected and tightened if necessary.
  • Modular System: The modular design allows for easy replacement of individual components if needed, though specific repair instructions are not detailed in this general overview.
  • Technical Assistance: Siemens provides technical assistance via telephone, fax, and email, as well as an online support portal (support.industry.siemens.com) for documentation and troubleshooting. This ensures that users have access to expert help for any maintenance or operational queries.