General information
Configuring SIRIUS Innovations
Configuration Manual, 04/2010, A8E56203880102-02
17
Load feeders with soft starters
Soft starters can also be used to prevent current peaks in the line supply instead of the
star(wye)-delta starting combinations. Three versions of these soft starters are available:
3RW30
3RW40
3RW44
The 3RW4 soft starters come as standard with an integrated solid-state overload relay. This
means that, in fuseless combinations, a motor starter protector is only required for short-
circuit protection. In the case of 3RW30 soft starters, the motor starter protector must also
cover the overload protection.
3RB22 / 23 overload relays and SIMOCODE pro
The modular, solid-state overload relays with external power supply type 3RB22 / 23 for
high-feature applications up to 630 A have been designed for inverse-time delayed
protection of loads with normal and heavy starting against excessive temperature rises due
to overload, phase unbalance or phase failure.
SIMOCODE pro is a flexible, modular motor management system for motors with constant
speeds in the low-voltage performance range. It provides the intelligent, communication-
capable interface between the higher-level automation system and the motor feeder.
A configuration with 3RB22 / 23 overload relays and with SIMOCODE pro requires in each
case a basic unit, a connection cable and a current measuring module. The MLFBs of the
current measuring modules are listed in the tables. Details of the basic units and connection
cables are given in the following:
3RB22 / 23
Basic unit (= evaluation module)
Monostable, screw: 3RB2283-4AA1
Bistable, screw: 3RB2383-4AA1
Monostable, spring-loaded: 3RB2283-4AC1
Bistable, spring-loaded: 3RB2383-4AC1
Connection cable
0.1 m (S00-S3): 3RB2987-2B
0.5 m (S00-S12): 3RB2987-2D
For other accessories for 3RB22 / 23 overload relays see Catalog LV 1 Chapter 5.

Table of Contents

Other manuals for Siemens SIRIUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIRIUS and is the answer not in the manual?

Siemens SIRIUS Specifications

General IconGeneral
Product brand nameSiemens
SeriesSIRIUS
Coil Voltage24V DC, 110V AC, 230V AC
Switching CapacityUp to 10A
Mounting TypeDIN rail
Product designationSIRIUS
Contact MaterialSilver alloy
Contact RatingVaries depending on the specific SIRIUS relay model (e.g., 6 A at 250 V AC, 10 A at 250 V AC)
Switching VoltageVaries depending on the specific SIRIUS relay model (e.g., 250 V AC, 400 V AC)
Mechanical LifeUp to 10 million operations
Electrical LifeUp to 100, 000 operations
Operating Temperature-25°C to +55°C
Protection ClassIP20
Size of relay baseVaries depending on the specific SIRIUS relay model