Selection tables 400 V AC
3.5 Motor starter protector + solid-state contactor
Configuring SIRIUS Innovations
Configuration Manual, 04/2010, A8E56203880102-02
41
Standard
three-phase motor
4-pole at
400 V AC
1)
Solid-state contactor
2)
Stan-
dard
output
P
Motor
current
(guide
value)
I
Setting range
Overload release
Motor starter
protector
Motor starter
protector
Mounting with lateral
clearance of 20 mm
Butt-mounting
3)
kW A A Order No.
Size
Order No. Order No.
Short-circuit breaking capacity I
q
= 20 kA
2,2 5 4,50 ... 6,30 3RV2011-1GA10 S00 3RF3405-1BB04 3RF3410-1BB04
3 6,5 5,50 ... 8,00 3RV2011-1HA10 S00
4 8,5 7,00 ... 10,0 3RV2011-1JA10 S00
3RF3410-1BB04 3RF3410-1BB04
Short-circuit breaking capacity I
q
= 5 kA
5,5 11,5 9,00 ... 12,5 3RV2011-1KA10 S00 3RF3412-1BB04 3RF3412-1BB04
7,5 15,5 11,0 ... 16,0 3RV2021-4AA10 S0
7,5 15,5 14,0 ... 20,0 3RV2021-4BA10 S0
3RF3416-1BB04 3RF3416-1BB04
Order numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link
module can only be used with screw terminals.
1)
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
2)
Rated currents taken into account at 40 °C ambient temperature. Rated control supply voltage 230 V AC, 50 Hz. Other
control voltages are also possible.
3)
The rated currents must be reduced if the solid-state contactor is butt mounted. Detailed characteristic curves can be
found in Chapter 3 of the SIRIUS Innovations System Manual.
See also
Industrial Controls System Manual - SIRIUS Innovations
(http://support.automation.siemens.com
/WW/view/en/39740306)