Equipotential Bonding 
   
 
 
© Siemens AG, 2004. All rights reserved 
EMC Installation Guideline – Planning Guide (EMV) – 03.2004 Edition 
4-23 
Equipotential bonding by means of equipotential bonding lines  
 
Central earthing bar
Cubicle
Equipotential bond. strip
P
P
P
P = Equipotential bonding conductor
Component 5
Component 6
Operator panel
To motor housing
P
Equipotential bond. strip
P
P
 1)
 
PE = Protective earth
 
1)  = PE in motor cable, also used as
    
equipotential bonding conductor
  
 1)
Component 1
Component 2
 Component 3
(Power component)
 Component 4
(SIMODRIVE)
Central earthing connector
 
Fig. 4-2  Equipotential bonding by means of equipotential bonding lines 
 
Arrangement: 
The distance between the signal lines (forward and return conductor) or between 
signal lines and the appropriate equipotential bonding lines must be as short as 
possible (bundle the lines!). The interference surface between the lines must be 
kept as small as possible. 
 
Cross-section: 
Cross-section of the equipotential bonding lines ≥ 10mm
2
 Cu.